cameroon gce A level 2024 design of electrical installation 2

cameroon gce A level 2024 design of electrical installation 2

cameroon gce A level 2024 design of electrical installation 2

THEME: ELECTRICAL INSTALLATION OF NEWLY CREATED TECHNICAL SCHOOL
The technical school is made lip of two workshops and an administrative block equipped with equipment. I he
administrative block is made of five offices. The line diagram of the installation is shown in figure I .
A
. Presentation of the installation

Load distribution
Location Loads
02 threephase squirrel cage induction motor of 3kW each, coscp 0.8, q = 0.88
02 single phase drilling machines of
1.5kW each, costp = 0.75, q = 0.75
04 three
phase welding machines of 4kW each, coscp = 0.8, q = 0.8
24 single sockets 2P+T, 220V
, 16A
06 three phase sockets
3P+T, 380 V, 20 A
j 01compressorsdrivingbyamotorabsorbs32kWeachandcoscp=0.8,q= 1
01
sander of 2kW, coscp = 0.8, q = 1
20 fluorescent
lamps of 40W, coscp = 0.9, q = I
01 three
phase compressor of 15kW, coscp = 0.92, q = 0.9
10
twin tube fittings compensated DUO connection for 20 fluorescent tubes of 40W,
coscp = 0.9, q = 1 , the power consumed by each ballast is evaluated as 20% of the tube
Workshop 1
power.
04 threephase welding machines of 4kW each, coscp = 0.8, q = 0.8
07 incandescent lamps of 75W each
03 three phase oven of 25kW
each
16 single phase sockets (2P+T), 220V, 16A, coscp = 0.8
08
single phase sockets (3P+T), 380V, 32A, coscp = 0.8
Workshop 2
Each office has the following equipment:
02 fluorescent lamps of 40W each, coscp = 0.9
, q = 1
01 fridge of 500W
, coscp = 0.9, q = 1
01 air conditions of 1.5hp each
, coscp = 0.8, q = 0.9
04 single phase sockets
(2P+T), 220 V, 16 A, coscp = 0.8
02 incandescent
lamp of 60W each

SECTION A: (COMPULSORY)
a) Determine the power demand by completing Appendix 1.
b) Considering the apparent power demand to be equal to 248kVA and by envisaging an extension of loads of 25%,
select using appendix 2 the characteristics of the transformer to be installed.
c) With the aid of appendix 3, determine the capacitance of the bank of capacitors to correct the power factor of
workshop 2 from 0.86 to 0.96 if the installed power is 146kW.
1 .
(30 marks)
(
5 marks)
(
5 marks)
SECTION B (OPTIONAL)
a) The cable from BB 1 to BB2 carries a current of 276A at a p.fof 0.85. This is made up of a PVC insulated copper
threecore cable which is installed touching 3 other multicore cables on perforated trays in an ambient
temperature of 40°C. Using appendix 4, 5 and 6, determine the crosssectional area of this cable. ^ (15 marks)
b) The cable from BB 1 to BB2 has a resistivity of 0.0225£lmm 2/m and linear reactance of 0.08* 10 T2/m. Calculate
the relative voltage drop if the length of the cable is 55m. 00 marks)
c) Using appendix 7, determine the short circuit current at the BB2 considering the upstream short circuit current of
9kA. (5 marks)
j.
a)

Considering the current of 375A absorbs by the whole installation, with the aid of appendix 8, select the circuit l.
breaker CKM by completing table 3. (5 marks)
Using appendix 8, what is the overload protection threshold current of a Compact NSJ600 circuit breaker u.
equipped with trip unit STR23SP? (5 marks)
Breaking capacity
Un(V) Number of poles
Circuit breaker Reference ln(A)

CKM
Table 3
b) One of the 3kW threephase squirrel cage induction motor in workshop 1 is replaced with a 7.5k W motor and the
starting
method of this motor is directonline. Using appendix 9 and 9, give the average fullload current of this

motor and select the various components for the control and protection of the motor. (10 marks)
4.
a) Using the data on the additional block, reproduce and complete table 4 by obtaining a balanced
installation. ( 12 marks)
Load Phase 1 current (A) Phase 2 current (A) Phase 3 current ( A )
3phase compressor
Single phase drilling machines
0 (8 marks)
2 . 2
Table 4
b)
I.
For each of the area of house, reproduce and complete table 5

Number of lighting
points
Type of
control
^Number of
socket outlets
Special
circuit
Area
Palour
Security
Table 5
By using PROMOTELEC Label
(norm) N < 5, give the number of subcircuits for lighting, socket
outlets and specialized circuits
.

(4 marks)
(6
marks)
iii. #
Draw the partition diagram indicating the crosssectional area of each conductor and the
range of each fuse used to protect the subcircuits.