THEME: ELECTRICAL INSTALLATION OF A FACTORY

The factory has three workshops and offices as represented on the electrical line diagram as shown in figure 1. The factory is supplied with a three-phase transformer 15 kV/ 380 V- 50 Hz installed at the entrance of the factory.

I. Structure of the line diagram

Diagram showing the transformer and distribution to Workshop n°1, Workshop n°2, Workshop n°3, and Offices.

Figure 1: Line diagram of the installation

II. Load distribution

WORKSHOP N° 1

Circuit -breaker Supply line Quantity Designation Characteristics
CB 1 AA1 12 2P+T Socket-outlets 220 V- 16 A
CB 1 AA1 06 3P+T Socket-outlets 380 V-20A; cos = 0.8
CB2 AA2 01 3-phase belt conveyor Pu = 5.5 kW; = 0.8; cos = 0.75
CB3 AA3 04 Auxiliary circuit lines S = 40 kVA; cos = 0.8
01 3-phase hoist Pu = 7.5 kW; = 0.86; cos = 0.8
CB4 AA4 01 3-phase rotative machine Pu = 3 kW; = 0.88; cos = 0.8
01 3- phase screw conveyor motor Pu = 4 kW; = 0.8; cos = 0.75
CB5 AA5 10 Fluorescent mercury discharge lamp 400 W – 220 V; cos = 0.8
Power loss in the ballast is evaluated at 25% of the rated power